C-Tec CA731 CAST Mains Switching Input Output Module
Product Details
- LPCB certified to EN54-17 & 18 and Kiwa Telefication & DBI certified to EN54-13.
- Also certified to the relevant parts of EN54 with Swedish certification body SBSC.
- A mains-switching version of our CA730 input output module.
- Capable of switching 5A @ 230 V AC or 5A 30V DC.
- Incorporates the functions of a switch monitor, zone monitor and output unit.
- Can be configured to monitor any combination of the following:-
• Up to 20 conventional detectors and 10 MCPs.
• Any normally open switch with an EOL resistor fitted.
• A simple normally open or closed switch (non-fault monitored). - Onboard short-circuit loop isolator.
- 6mA typical alarm current (1.7mA typical quiescent current) @ 22-40V DC.
- Indicators for Loop polling, input faults and relay status.
- Includes volt free changeover contacts that can be used to trigger rollershutter doors, gas shut-off valves, smoke vents, etc.
- Mountable on a C-TEC NCP-26 surface box or a standard UK 25mm double gang back box (not supplied).