Hager JK112BG 125A 12 Way TPN Board w- Glazed Door
Product Details
- Standards Designed, manufactured and tested to BS EN 61439-3
- Busbar Current Rating: 125A
- Busbar Type Fully shrouded copper
- Busbar Rating 25kA Conditional
-
Incoming:
- 100A Switch
- 125A Switch
- 63A contactor AC3
- 100A contactor AC3
- Direct connection
- RCCB incomers
- Outgoing Ways: 12
-
Outgoing Protection:
- Type B MCB (6A to 63A, 1P & 3P)
- Type C, D MCB, (0.5A to 63A, 1P & 3P)
- 1Mod and 2Mod RCBO
- Voltage Rating in AC: 230 / 415V
- IP Protection: IP3X to BS EN 60529
- Enclosure Body Type: Steel
- Cable Entry: Obround protected cable entry points
- Terminal Connection Capacity:
- Incoming Line Terminal: 50mm2
- Incoming Earth Terminal: M8 stud
- Incoming Neutral Terminal: 50mm2 cage or M6 stud
- Outgoing Earth Terminals: 16mm2
- Outgoing Neutral Terminals: 16mm2
- Enclosure Earth Stud: M8
-
Mounting:
- 4 x key hole fxing holes plus central top key hole for one fxing hanging / levelling
- Surface Wall Mount
- Gland Plate: Top and bottom removable
- Integrated Locking System: Coin lock as standard, key lock as accessory
- Protection index IP: IP30
Protection class: Protection class III
Specification
Amps ii |
125 |