Schneider A9F54232 Acti9 iC60H 2P 32A C-Curve MCB
Product Description
- poles description: 2P
- number of protected poles: 2
- [In] rated current: 32A
- network type: AC
- trip unit technology: Thermal-magnetic
- curve code: C
-
breaking capacity
- 10 kA Icu at 100...133 V DC conforming to EN/IEC 60947-2
- 10000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
- 42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2
- 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
- 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
- 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
- network frequency: 50/60 Hz
- [Ue] rated operational voltage: 440 V AC 50/60 Hz
- magnetic tripping limit: 8 x In +/- 20 %
- limitation class: 3 conforming to EN/IEC 60947-2
- [Ui] rated insulation voltage: 500 V AC 50/60 Hz conforming to EN/IEC 60947-2
- [Uimp] rated impulse withstand voltage: 6 kV conforming to EN/IEC 60947-2
- contact position indicator: Yes
- control type: Toggle
- local signalling: Trip indicator
- mounting mode: Clip-on
- mounting support: Rail
- 9 mm pitches: 6
- height: 85 mm
- width: 36 mm
- depth: 78.5 mm
- net weight: 0.25 kg
- provision for padlocking: Padlockable
-
connections - terminals:
- Single terminal (top or bottom) 1…25 mm ² rigid
- Single terminal (top or bottom) 1…16 mm ² flexible
- wire stripping length: 14 mm for top or bottom connection
- tightening torque: 2 N.m top or bottom
-
earth-leakage protection: Separate block
standards:
- EN/IEC 60947-2
- EN/IEC 60898-1
-
IP degree of protection: IP20 conforming to IEC 60529