Product Details

  • Number of poles: 3P

  • [In] rated current: 160A at 40 °C

  • [Ue] rated operational voltage: 690 V AC 50/60 Hz conforming to EN/IEC 60947-2

  • Suitability for isolation: Yes conforming to EN/IEC 60947-2

  • Utilisation category: Category A

  • [Icu] rated ultimate short-circuit
    breaking capacity: 36 kA Icu at 415 V AC 50/60 Hz conforming to EN 60947-2

  • Performance level: F

  • Trip unit name: TM-D

  • Trip unit technology: Thermal-magnetic

  • Trip unit protection functions: LI

  • Control type: Toggle

  • [Ui] rated insulation voltage: 800 V AC 50/60 Hz conforming to EN/IEC 60947-2

  • [Uimp] rated impulse withstand
    voltage: 8 kV conforming to EN/IEC 60947-2

  • [Ics] rated service short-circuit
    breaking capacity: 36 kA at 415 V AC 50/60 Hz conforming to EN/IEC 60947-2

  • Mechanical durability: 40000 cycles

  • Electrical durability:
    • 40000 cycles at 440 V In/2
    • 20000 cycles at 440 V In
    • 15000 cycles at 690 V In/2
    • 7500 cycles at 690 V In

  • Protection type:
    • L : for overload protection (long time)
    • I : for short-circuit protection (magnetic)

  • Long-time pick-up adjustment type Ir (thermal protection): Adjustable

  • [Ir] long-time protection pick-up adjustment range: 63...160 A

  • Long-time protection delay adjustment type tr: Fixed

  • [Tr] long-time protection delay adjustment range:
    • 400 s at 1.5 x Ir
    • 16 s at 6 x Ir
    • 11 s at 7.2 x Ir

  • thermal memory : 20 minutes before and after tripping

  • Short-time protection pick-up adjustment type Isd: Adjustable

  • [Isd] Short-time protection pick-up adjustment range: 1.5...10 x Ir

  • Short-time protection delay adjustment type tsd: Fixed

  • Instantaneous protection pickup adjustment type Ii: Fixed

  • [Ii] instantaneous protection pick-up adjustment range: 2400 A

  • Dimensions (HxWxD): 161 x105 x 86mm

  • Net weight 2.05 kg

  • Standards:
    • EN/IEC 60947-1
    • EN/IEC 60947-2

  • Pollution degree 3 conforming to IEC 60664-1

  • IP degree of protection: IP40 conforming to IEC 60529

Specification

Mcbrcboincomerrccb amps

160A

No of mcbrcborcd poles

3 Poles